Medium Voltage – Automatica SA https://automatica.ro Mon, 03 Dec 2018 14:10:47 +0000 en-GB hourly 1 https://automatica.ro/wp-content/uploads/2018/08/favicon-150x150.png Medium Voltage – Automatica SA https://automatica.ro 32 32 Medium voltage switchgear with automated circuit breaker https://automatica.ro/en/servicii/prezentare-celula-medie-tensiune-smart-grid-en/?utm_source=rss&utm_medium=rss&utm_campaign=prezentare-celula-medie-tensiune-smart-grid-en https://automatica.ro/en/servicii/prezentare-celula-medie-tensiune-smart-grid-en/#respond Fri, 31 Aug 2018 11:19:59 +0000 http://exclusiveweb.info/automatica-ro/?post_type=servicii&p=13422

Automatica has designed and certified a new type of medium voltage cell. This new type of cell can withstand currents of 50kA short circuit and can be integrated into a SCADA system because of the automated CLP and circuit breaker rail.

]]>
https://automatica.ro/en/servicii/prezentare-celula-medie-tensiune-smart-grid-en/feed/ 0
Medium voltage reactive power control https://automatica.ro/en/servicii/compensare-putere-reactiva-medie-tensiune-en/?utm_source=rss&utm_medium=rss&utm_campaign=compensare-putere-reactiva-medie-tensiune-en https://automatica.ro/en/servicii/compensare-putere-reactiva-medie-tensiune-en/#respond Fri, 31 Aug 2018 11:19:27 +0000 http://exclusiveweb.info/automatica-ro/?post_type=servicii&p=13419

Industrial consumers, in general, pay monthly for a quantity of reactive energy representing the difference between the measured reactive energy and the calculated reactive energy, corresponding to the neutral power factor (0,92).

In order to eliminate these expenses, the improvement of the power factor is done through the injection of capacitive reactive energy in the consumer’s distribution network.
Control systems are used with ecological capacitor banks of fixed value or sequential, installed at the level of 6, 10 or 20 kV, indoor or outdoor.

Each power factor correction switchgear is equipped with exhaust hatches in case of internal incidents (arc fault, capacitors’ defects).

Technical data

Measurement unit

Nominal values

Rated voltage

kV

6,3

Frequency

Hz

50

Withstand voltage 1 min. at 50 Hz

kV

28

Power allowance

-5%….+10%

Discharge time up to 75 V

S

600 max

Losses

w/kVar

0,3

Operating temperature

-10oC….+40oC

Standards

IEC 60871-1

EN 60871-1

The capacitor banks in each switchgear are powered through a three-pole disconnector, with fuses and circuit breaker, when you require a manual actuation, or through a fuse contactor when you require an automated (sequenced) actuation, each sequence having circuit breaker.

]]>
https://automatica.ro/en/servicii/compensare-putere-reactiva-medie-tensiune-en/feed/ 0
Medium voltage enclosure https://automatica.ro/en/servicii/caseta-medie-tensiune-en/?utm_source=rss&utm_medium=rss&utm_campaign=caseta-medie-tensiune-en https://automatica.ro/en/servicii/caseta-medie-tensiune-en/#respond Fri, 31 Aug 2018 11:17:42 +0000 http://exclusiveweb.info/automatica-ro/?post_type=servicii&p=13413
  • Within the medium voltage enclosure voltage measurement transformers can be installed on a withdrawable truck.
  • The medium voltage enclosure for switchgears modernizations is designed for the replacement of the existing circuit breakers in the medium voltage switchgear, thus insuring the simple and safe extraction of the modern vacuum or SF6 circuit breaker.
  • All the mechanisms of the medium voltage enclosure are designed and manufactured to offer maximum user safety and convenience of use.
  • The medium voltage enclosure can be fitted with a whole range of circuit breakers within the medium voltage switchgears:
    • capacitor bank;
    • transformer;
    • radial line;
    • interconnected line;
    • motor;
    • couple;
    • input.
Technical data UM Value
7.2kV 12kV 24kV
1. 2. 3. 4. 5.
Rated voltage kV 7,2 12 24
Operational voltage kV 6 10 20
Testing voltage 50Hz 1 min kVef 20 28 50
Lighting impulse testing voltage kVmax 40 75 125
Rated frequency Hz 50/60
Rated current A 630 – 2500
Short time withstand current, 1s kA 16 – 50 16 – 50 16 – 31,5
Peak withstand current Ipk (Ka) kA 40 – 125 40 – 125 40 – 80
Protection degree (CEI 60529) IP 31
Surfaces treatment zinc plated/powder coating
]]>
https://automatica.ro/en/servicii/caseta-medie-tensiune-en/feed/ 0
Medium voltage switchgears 7,2 kV, 12 kV, 24kV https://automatica.ro/en/servicii/celule-medie-tensiune-72kv-12kv-24kv-en/?utm_source=rss&utm_medium=rss&utm_campaign=celule-medie-tensiune-72kv-12kv-24kv-en https://automatica.ro/en/servicii/celule-medie-tensiune-72kv-12kv-24kv-en/#respond Fri, 31 Aug 2018 11:17:07 +0000 http://exclusiveweb.info/automatica-ro/?post_type=servicii&p=13411

The medium voltage switchgear is designed for the primary distribution of the medium voltage electrical energy in power substations, industrial substations, secondary distribution substations.

Type CI/CE indoor/outdoor electrical switchgears are designed for rated voltage of 7,2; 12; 24 kV and rated current up to 4000 A.

Applications:

  • Thermal-electrical plants,
  • Hydro-electrical plants,
  • Nuclear-electrical plants,
  • Mining industry,
  • Naval industry,
  • Oil industry,
  • Chemical industry,
  • Subscriber transformer posts,
  • Airports,
  • Transformer stations and substations.

The indoor medium voltage switchgear is made of metallic elements assembled to form compartments with simple/double busbar system, aer insulated.  It can be manufactured withdrawable version (with truck) or fixed version (without truck). It can be equipped with vacuum circuit breakers (SIEMENS, ALSTOM, SCHNEIDER, EATON, ABB, TAVRIDA, or others) or SF6 (ABB, ALSTOM, SCHNEIDER, or others) or air or SF6 disconnectors (SIEMENS, ALSTOM, EATON, ABB) .

Versions:

  • Indoor or outdoor,
  • Transformer outgoing panel,
  • Coupler panel with circuit breaker,
  • Coupler panel without circuit breaker (dummy truck),
  • Outgoing feeder panel,
  • Motor panel,
  • Capacitor bank panel,
  • Voltage measurement panel,
  • With/without surge arresters,
  • Auxiliary transformer panel.

The switchgears are built so that all operations and maintenance operations including regular checks of the phases’ succession, earthing connections, cable’s fault detection and dielectric tests can be done in safe conditions.

Thanks to a high degree of automation the switchgears can be integrated in a remote control SCADA monitoring system.

The switchgear can be equipped with devices from our traditional suppliers SIEMENS, ALSTOM, SCHNEIDER, EATON, A

BB, TAVRIDA or devices from other producers according to our customers’ requirements.

]]>
https://automatica.ro/en/servicii/celule-medie-tensiune-72kv-12kv-24kv-en/feed/ 0